Mike Nager
Phoenix Contact,
Americas R.B.U.
Harrisburg, Pa.
Thermocouples aren’t exactly the
latest fad in automation and control.
They’ve been in use for a long time,
work well, and seem pretty simple
in operation. More than 60% of all
temperature measurements in the
U.S. use thermocouples.
There are good reasons to use
thermocouples over other temperature
sensors. Your facility may
already use them. The application
may need a sensor that withstands
a lot of physical stress or one that is
physically small. The expected high,
low, or span of temperature may exceed
the limitations of other sensor
types. Finally, it might be difficult to
justify a higher price for more sophisticated
devices.
Perhaps the most common misconception
about thermocouples
is that the signal is created by the
thermocouple junction, like some
sort of miniature battery. A thermocouple
voltage is actually generated
along an entire length of wire that
has a temperature gradient.
A useful concept to keep in mind concerns
the relationship between
heat and electrical energy within
electrical conductors including
thermocouple wires. As a demonstration,
hold a single piece of wire
on one end and then heat the opposite
end. You’ll quickly discover
that the heat moves up the wire. It
does so because the hot atoms impart
some of their kinetic energy to
their colder neighbors.
The more kinetic energy an atom
has, the faster it vibrates. Atoms
with the highest kinetic energy are
at the hot end of the wire, so they
vibrate the most. While the nucleus
of the atom remains trapped within
the solid structure of the wire, some
outer electrons are free to move. The
vibrating atoms force free electrons
toward the cold end and spread the
kinetic energy in the form of heat
conduction.
Because electrons have a negative
charge, their forced migration
creates a positive potential at the
hot end of the wire and a negative
potential at the cold end. The magnitude
of the voltage depends on
the composition of the wire and the temperature difference between the
hot and cold ends. The length or
gage size of the wire has no effect on
the voltage generated.
Although there is electron movement
in any single conductor, it is
virtually impossible to get a voltage
measurement from it. Readers
will recall voltage is the difference
in electrical potential between two
points. Trying to take a voltage
reading from a single point on the
wire just can’t be done.
To get around this limitation, a
second wire made from a different
metal or alloy attaches to the first
wire at the high-temperature point.
The connection is called the “hot
junction.” Different metals produce
different quantities of electron motion
when the wires are heated to
the same temperature. The imbalance
between the number of electrons
creates a potential difference
(voltage) between the wires.
Any other point those wires connect,
including terminal blocks and
measuring instruments, is called a
“cold junction.” One cold junction
at the place thermocouples connect to the measuring instrument
is unavoidable. This is often called
the reference junction. Temperature
readings made at the reference
junction correct any thermocouple
voltage generated there in a process
called cold junction compensation.
Thermocouple circuits can have
more than one cold junction, but
that is strongly discouraged and
easily avoided.
The raw voltage signal that represents
temperature is the sum of
all the hot and cold junctions. The
temperature of the hot junction is
determined by subtracting the offsets
generated by all of the cold junctions.
Thus the output voltage of the
thermocouple depends only on the
temperature of the hot junction.
The materials used to create the
hot junction determines the type
of thermocouple. The material type
to use for a given application depends
on temperature range and
environmental conditions. Four
types of thermocouples, identified
by the letters K, J, T and E, account
for more than 99% of all thermocouple
applications.
Practical Measurements
The voltage thermocouples
generate is small often less than
30 μV/°F. Such low potential is easily
corrupted by noise. Typically, the
microvolt signal feeds a transmitter
that converts it into a robust process
signal, such as a 4-to-20-mA instrumentation
current loop. Transmitters
have become economical with
some priced in the $150 range. The
low cost lets them serve in noncritical
applications.
It’s fairly common to use transmitters
that fit in a thermowell probe
when connecting thermocouples
with runs from several hundreds to
thousands of feet. Thermowells are
closed metal tubes that extend into
the region where temperature measurements
are made. The hockey-puck
shaped transmitter fits in the
exposed end of the well while the
the rmocouple
extends into the
other end.
Hockey-puck style
transmitters
work well for
hazard-classified
areas. The transmitters
mount in
metal probes with
sealed covers and
connect securely
to metal conduit
that meets the various
encapsulation or explosion-proof requirements.
Intrinsically safe circuits are used to
power the device while conduit fittings
protect the wires mechanically.
Hockey-puck transmitters are generally
output loop-powered, meaning
they are powered from a supply
back in the control cabinet.
DIN-rail-mounted transmitters
are most widely used in automation
applications, such as those in sealing
operations on packaging machines.
The length of wire needed is often
a fraction of that found in process
applications. So it is reasonable to
run the thermocouple wires back
to a control cabinet or junction box
for conversion. Also, thermowells
found in the process industries may
not be well suited for physical installation
on a machine. Embedded
thermocouples with tape or bolt-on
connections are often used inside
machine components.
Electrical isolation is important to
consider when deciding on a transmitter. Isolation between the thermocouple
input and output circuit
on loop-powered devices prevents
ground loops from degrading the
temperature signal. Typical isolation
values are in the 1 to 2-kV range.
Transmitters that get their operating
power from an external dc power
supply need additional isolation.
Often called three-way isolation, it
provides similar levels of protection
between input/output, input/power
supply, and output/power supply.
Isolation also provides a degree of
protection for the measuring devices
in the control cabinet in case
the thermocouple somehow touches
a high-voltage source.
Field Connections
If a transmitter is impractical,
then it may be possible to extend the
length of the thermocouple wires by
using special terminals mounted in
the thermowell or surface-mounted
on the machine. The connection
area should be away from extreme
process temperatures. In fact, temperatures
should be close to that of
the controller. Thermocouples are
wired to terminals specially constructed
to minimize any temperature
difference between their two
ends and between each individual
wire. These terminals are sometimes
referred to as “isotherm” blocks.
Isotherm blocks allow the famous
“Law of Intermediate Metals”
to operate. This law states that if all
connection points on the isotherm
block are of equal temperature, adding
a third metal in both wires of the
circuit won’t degrade the signal.
With the thermocouple connected
to one side of the isotherm
block, the other side connects the
special thermocouple extension or compensation wire. Technically, extension
wires have the same chemical
composition as their thermocouples,
while compensation wires
have a different composition. In
practice, though, the extension cable
term is most often used regardless
of the wire composition.
Extension cables can cost up to
50% less than thermocouple wire.
They also come in sizes up to
14 awg, which reduces loop resistance
in long runs. Between 0 and
200°F, extension cables exhibit the
same electrical properties as the
thermocouples themselves and
are electrically indistinguishable
from thermocouple wire. To keep
extension wire from inadvertently
being used as thermocouple wire,
the outer insulation jacket on the
extension wires is color coded differently
than the outer jacket on
thermocouple wires. However, the
individual wire insulation color
matches that of thermocouple
wire.
Convention for both thermocouples
and extension wires calls
for a “P” to be used to indicate the
positive leg and an “N” for the negative.
Extension wires are also designated
by the letter “X.” So a “JP”
designation refers to the positive leg
of a Type J thermocouple. “KNX”
refers to the negative leg of a Type K
extension cable.
Cabinet Connections
Extension wires typically run into
distributed control systems, PLCs,
or temperature analyzers back at the
control cabinet. For the very best results,
a user would run one continuous
piece of wire from the hot junction
to the terminals on the measuring
instrument. But often this isn’t
practical. Cabinets built off-site and
by third-parties can’t be wired directly.
Therefore, terminal blocks
are used to help make wiring easier. The panel shop wires from the controller
to the terminal block, leaving
the other side open for the field connection
of the extension wire.
There is an unfortunate widespread
belief that thermocouples
can simply connect to standard
terminal blocks without degrading the signal, using the Law of Intermediate
Metals as the rationale.
The contact area and current bar
in most terminal blocks is made of
steel, though high-quality blocks
use nickel-plated-copper alloy. Either
material forms a cold junction
because it doesn’t match the
chemical composition of the thermocouple
wire. As mentioned in
the last section, it’s possible to use terminal blocks without making a
cold-junction correction. But that
works only if the temperature on
both sides of the block remains the
same or changes at exactly the same
rate. That isn’t likely in control cabinets
packed with heat-producing
equipment, fans, and other devices
that heat and cool the interior unevenly.
Standard terminal blocks
are not designed to minimize temperature
differentials like isotherm
terminals. They make the measurement
unpredictable whenever a
heat-generating device is switched
on or off or the cabinet is opened.
The solution is to use thermocouple
blocks whose metal parts
match the composition of the thermocouple
extension wire. Because
the materials match, there is no
cold junction. To the thermocouple
circuit, it looks like a continuous
piece of extension wire. Changing
temperature won’t introduce errors.
Thermocouple blocks are typically
more expensive than standard terminal
blocks, but eliminate a potentially
tedious source of errors.
Temperature Control
Main system controllers, whether
PLC, PC, or DCS, no longer need to
perform temperature control. It may
be preferable to “outsource” or distribute
that control to another device.
For example, DIN-rail-mounted
temperature transmitters convert
low-level thermocouple signals to
4-to-20 mA and electrically isolate
the circuit from ground loops. Some
allow simple ON/OFF control with
programmable dead bands using a
transistor or relay output while others
may also incorporate displays.
Other devices measure several
thermocouples at once using sophisticated
control algorithms to do more
advanced control than simple ON/
OFF. Proportional, integral, and derivative
(PID) control has been used
for decades and is rapidly finding applications
in the discrete world. In
applications like heat seal packaging
and extrusion processes, temperatures
must be controlled rapidly and
precisely. Heat must be added or removed
in fractions of a second.
One of the latest devices for temperature
monitoring uses a communication
bus controlling and transmitting
temperatures. Because they
typically mount in a junction box on
standard DIN-rail, they can reside
close to the thermocouples, reducing
possible sources of error. The input filtering, control logic, and
process output all take place in the
device. There is no need to stretch
PLC resources trying to process the
PID loops. And because the device is
part of a bus network, the information
can be sent out via standard industrial
protocols such as Ethernet, Interbus, Profibus, or DeviceNet.
Other I/O signals can be added for
analog, digital, or serial devices.
Troubleshooting hints
A few problems show up regularly
in thermocouple applications.
Watch out for wires that are damaged or broken by rough installation,
vibration, or other stress.
Take care not to reverse the polarity
of the thermocouple loop.
Remember that USA standard
ASTM E 230 dictates the negative
leg always has red insulation and its
symbol is the thicker wire. The first named element of a thermocouple
is always positive.
Uncompensated cold junctions
cause many problems in areas
where stable temperatures can’t be
guaranteed, which is just about everywhere.
Only use thermocouple
or extension wire in the circuit. Be
suspicious of any standard nonisotherm
or nonthermocouple terminal
blocks in the loop.
Make sure the loop resistance
isn’t too high. The maximum value
you should shoot for is usually 100
Ω. Remember that total length is
twice the actual length because there
is both a supply and return wire
length. Use wire tables or test the
cable to determine its resistance.
Keep thermocouple wires away
from other current-carrying conductors,
motors, and sources of
radio frequency noise. If in doubt
(that is, always), convert the thermocouple
voltage to a more robust
signal like a 4-to-20-mA instrumentation
loop.
When using thermocouples from
outside the U.S., verify the color
coding is correct. Europe and Japan
use different conventions than the
standards that originated in the U.S.
The varying conventions have been
used for more than 60 years in their
respective countries, so there is little
chance of further “harmonization”
in the future.
Many affordable products exist
that can simplify and enhance thermocouple
measurements. Transmitter,
meter, and switch prices
have become low enough to avoid
many traditional difficulties using
thermocouples. This also allows
consideration of new temperature
measurements that were either too
expensive or too complicated in the
past. Finally, conversion to a process
control signal (4-to-20 mA) or
a digital signal allows long-distance
transmission without having to
worry about the quirks of a thermocouple
circuit.
Make Contact
Phoenix Contact USA, (800)888-7388, phoenixcon.com
Power supplies and
thermocouple loops
Temperature loops that use thermocouple
transmitters require steady and reliable
24-Vdc power for all components
to work correctly. Most supplies are
now switch-mode, giving users several
advantages that include low purchase
price, light weight, and long life. These
modern supplies have efficiencies in the
90% range for more economical operation
and lower expenditures for cabinet
cooling equipment and operation.
From a purely technical standpoint,
selecting a power supply means finding
one that accepts a convenient input
voltage and provides enough amperage
to drive all the loads. Supplies can come
in a wide-range of input voltages with
output currents up to 40 A.
Supply location also plays an important
role in the selection process.
For example, supplies listed with
UL1604 Class I, Div. 2 ratings limit
the escape of electrical and heat energy
for safe use in areas that may contain
explosive vapors.
NEC Class 2 power supplies find use
in or on machines because that class
limits the amount of energy they can
produce to 100 W or less, or about 4.2 A
at 24 Vdc. Wires connected to that type
of supply do not need conduit runs.
A recent innovation in control
power is the 24-Vdc uninterruptible
power supply, or UPS. The UPS system
combines a power supply, battery, and a
charging circuit in one box. In the event
of power loss, the UPS maintains voltage
long enough to ride through the
outage or provide an orderly shutdown
if the outage lasts too long. |
Thermocouple transmitters
typically convert weak millivolt
signals from the thermocouple into
robust 4-to-20-mA process control
signals. Thermowell-mount circular
(hockey puck) and DIN-rail cabinet
mount transmitter styles perform
identical functions.
Connectors and terminal blocks
specifically designed for thermocouple
installations have contacts made of the
same material as the thermocouple to
prevent the formation of cold junctions.